Print version      Site map     
You are located here: Home > Product information > Twin wall insulated flue > MF > Technical details

Technical characteristics Metaloterm® MF

Application

 

 

 

 

 

Chimney/Flue system

Operating mode

 

 

 

 

 

Dry/wet

Pressure

 

 

 

 

 

Negative/positive pressure

Max. working pressure

 

 

 

 

 

200 Pa

Operating temperature  

 

 

 

 

 

450°C negative pressure

200°C positive pressure

Max. temperature allowed

 

 

 

 

 

1000°C negative pressure (max. 30 min.)

200°C positive pressure

Inner wall

material

 

 

 

 

AISI 316L/EN 1.4404

 

thickness

 

 

 

 

minimal 0.4 mm

Outer wall

material

 

 

 

 

AISI 304/EN 1.4301

 

thickness

 

 

 

 

minimal 0.5 mm

Insulation

type

 

 

 

 

Rockwool

 

thickness

 

 

 

 

Ø100 - 400: 25 mm

Ø450 - 600: 37.5 mm

Sealant

 

 

 

 

 

Elastomer

Fuel type

 

 

 

 

 

Wood/coal/oil/natural gas/calor gas/propane gas

 

CE

EN 1856-1:

T200-P1-W-V2-L50040-O10

T450-N1-D-V3-L50040-G50

T450-N1-W-V2-L50040-O40

EN 1856-2:

T200-P1-W-V2-L50040-O10

T450-N1-D-V3-L50040-G70

T450-N1-W-V2-L50040-O40

 

The clearance to combustible materials, as indicated in the CE-designation, applies to flues with a nominal diameter up to and including 300 mm. Regarding flues with a larger nominal diameter, the clearance must be multiplied b a factor: ø350 - ø450 x 1.5, ø500 - ø600 x 2, > ø700 x 4.

 

Applications Metaloterm® MF

  • Atmospheric gas-fired boilers
  • Condensing boilers
  • Wood-fired stoves
  • Industrial ovens, large-scale establishments

 

Advantages Metaloterm® MF

  • Universal chimney/flue system
  • Inner- and outer wall from high quality stainless steel
  • No therminal bridges, uninterrupted insulation from base plate to top stub
  • Stress free thermal expansion
  • Fast-build system without the need of sealants
  • Compatible with system Metaloterm® ME and UE
  • High density and high quality insulation
  • High-temperature silicone sealing ring
  • Lightweight elements
  • Immediately ready for use

 

 

Inner diameter

mm

100

130

150

180

200

250

300

350

400

450

500

600

Outer diameter

mm

150

180

200

230

250

300

350

400

450

525

575

675

Cross section

cm2

79

133

177

254

314

491

706

962

1256

1590

1963

2826

Weight

±kg/m

4.5

5.5

6.0

7.0

7.5

9.5

12

15

19

23.5

27.5

32

 